Omron SYSMAC CS1W-CLK13 Operation Manual page 218

Optical ring controller link units, h-pcf/gi cable
Table of Contents

Advertisement

Setting Routing Tables
Controller Link System
Network address A
PLC
acting as
bridge
Unit number d
Unit number c
Unit number b
Unit number a
Example 2
SYSMAC NET Link System
Network address B
SYSMAC BUS/2 System
CLK SNT RM BSC CPU PS
Do not register SYSMAC BUS/2 Master Units and BASIC Units in local net-
work tables because these Units do not connect to networks.
The following example show the settings for a relay network table connecting
three networks.
PLC 1
Node address a
Network
PLC 2
address A
Node address b
Node address c
PLC 3
Network
Node address d
address B
PLC 4
Node address e
Node address f
PLC 5
Network
address C
Node address g
On closer examination of the relay network table for PLC3, we see that the
relay network is B and the relay node is c when network A is the destination,
and that the relay network is B and the relay node is e when network C is the
destination.
PS:
Power Supply Unit
CPU: CPU Unit
SNT: SYSMAC NET Link Unit
CLK: Controller Link Unit
RM:
SYSMAC BUS/2 Remote I/O Master
BSC: BASIC Unit
Local Network Table
Loc
SIOU
No.
Netwk
unit #
(d)
A
1
(c)
B
2
Relay Network Tables
End
No.
Netwk
PLC ID Netwk
1
B
2
C
End
No.
PLC ID
Netwk
1
C
End
No.
Netwk
PLC ID
1
A
2
C
End
No.
Netwk
PLC ID
1
A
End
No.
PLC ID
Netwk
1
A
2
B
Section 7-4
Relay
Node
A
b
A
b
Relay
Netwk
Node
B
e
Relay
Netwk
Node
c
B
e
B
Relay
Netwk
Node
B
c
Relay
Netwk
Node
C
f
C
f
195

Advertisement

Table of Contents
loading