Manual Setting - Omron SYSMAC CS1W-CLK13 Operation Manual

Optical ring controller link units, h-pcf/gi cable
Table of Contents

Advertisement

Setting Data Links
5-2-2

Manual Setting

Transferring from a Programming Device
IBM PC/AT or
compatible
Setting data link tables
Note
Transferring from a Computer Node
Transfer the data link tables that were created on the Controller Link Support
Software (Ver. 2.00 or later) or CX-Net (in CX-Programmer) to the Controller
Link Unit or the Controller Link Support Board (for IBM PC/AT or compatible
computers).
The data link tables are transferred from a computer running the Controller
Link Support Software (Ver. 2.00 or later). The computer can either be a node
in the network or a computer attached as a Programming Device.
+
Controller Link
Support Soft
Transmissions
ware (Ver. 2.00
or later) or CX-
Net (in CX-Pro-
grammer)
1. When transferring data link tables to a CS-series PLC, set pin 1 of the DIP
switch on the CPU Unit to "OFF." Otherwise, data link tables cannot be writ-
ten normally.
2. When transferring the data link tables to a CVM1 or CV-series PLC, set the
System Protect Key switch on the CPU Unit to "NORMAL." Otherwise, data
link tables cannot be written normally.
3. The Controller Link Support Software (Ver. 2.00 or later) can be integrated
into the SYSMAC Support Software. Refer to the Controller Link Support
Software Operation Manual (W308) for details.
IBM PC/AT or compatible
computer
Controller Link
Support Software
Controller Link
Support Board
Setting data link tables
A data link table is created for each node using the Controller Link Support
Software (Ver. 2.00). The data link tables contain all the settings required to
create the data links.
CS-series PLCs
CVM1 and CV-series PLCs
Controller
Link Unit
Nodes
CPU Unit
Section 5-2
Controller
Link Unit
Nodes
CPU Unit
95