Omron SYSMAC CS1W-CLK13 Operation Manual page 329

Optical ring controller link units, h-pcf/gi cable
Table of Contents

Advertisement

Changing the Data Link Tables with Active Data Links
Procedure
1,2,3...
306
Node 1
Node 2
Node 3
Data link area
Node 1
Node 2
Node 3
In this example, by adding node 4 to the
network, the receive area from node 4 is
added to the data link table of node 1.
1. Create the new data link table to be transferred to the node whose data link
table is to be changed (node 1) offline.
2. Save the created data link table in a file.
3. Connect the personal computer to CX-Net so that it is online.
4. Select Data Link − Setup from the Menu.
5. Open the data link table file saved in step 1.
6. Use the mouse to select node 1, whose data link table is to be changed.
7. Select Online − Transfer to PLC while datalink active from the Menu.
Node 4
Newly added node
Node 4
The table contents are as follows:
Area 1: DM Area
First word: DM 00000
Send and receive words: 10 words each
Section 11-2