Omron F3SG-PGA-A User Manual page 281

Safety light curtain f3sg sr series multi-beam safety sensor
Hide thumbs Also See for F3SG-PGA-A:
Table of Contents

Advertisement

No.
Function name
1
Muting Time
Enter values of Muting-related time limits.
Information
For the Muting time input time limit and the Muting time limit,
setting the value to zero means the time limit is infinite.
Standard muting
Exit-only muting
Position detection muting
2
Check installation
Reflects the Muting Time Information settings to the timing
position
chart shown in the left side of the screen, and allows data entry
to the Input Information fields.
3
Input Information
Enter information about the work-piece.
4
Diagnosis of
It is diagnosed and displayed if the setting condition is
installation
appropriate.
condition
5
Evaluate
Checks if the muting with the entered settings is possible.
6
Installation
Shows the positions and timing chart of a work-piece, the
diagram and
F3SG-SR/PG and muting sensors. You can also make settings
Timing chart
to the muting time information by editing the values in the
timing chart directly.
7
Close
Finishes the setting process of muting time information, and
returns to muting setting.
If using this function together with other functions, make settings taking the condition of adjacent zones into account.
For more information on zone adjacency conditions, refer to 2-19. Setting Zone Adjacency Conditions.
When changing the settings is complete, confirm the settings and write the configuration to the F3SG-SR/PG.
To enable the written configuration, refer to 4-2-7-3. Writing Configuration into Intelligent Tap.
When connecting the Intelligent Tap to a F3SG-SR/PG and trying to return the F3SG-SR/PG to [Detecting], follow step 4
of 4-1-3-2. Connection Procedure When Using USB Connector to restart the F3SG-SR/PG and Intelligent Tap, or click
the [Monitor]
button.
Description
T1min: Muting input time limit
(Min. value)
T1max: Muting input time limit
(Max. value)
T2: Muting time limit
T3: Maximum allowable
muting signal interruption
T1min: Muting input time limit
(Min. value)
T1max: Muting input time limit
(Max. value)
T2: Muting time limit
T3: Maximum allowable
muting signal interruption
T4: Muting end waiting time
T5: Exit-only muting delay time
T1max: Muting input time limit
(Max. value)
T2: Muting time limit
T3: Maximum allowable
muting signal interruption
Setting with SD Manager 3
Initial
Configurable value or
value
numerical range
-
-
0.1 s
0.1 to 3.9 s (in 0.1 s
increments)
4 s
0.2 to 60 s (in 0.1 s
increments)/infinite
60 s
1 to 600 s (in 1 s
increments)/infinite
0.1 s
0.1 to 20 s (in 0.1 s
increments)
0.1 s
0.1 to 3.9 s (in 0.1 s
increments)
4 s
0.2 to 600 s (in 0.1 s
increments)/infinite
60 s
1 to 600 s (in 1 s
increments)/infinite
0.1 s
0.1 to 4 s (in 0.1 s
increments)
1 s
0.1 to 20 s (in 0.1 s
increments)
4 s
4 to 20 s (in 0.1 s
increments)
4 s
0.2 to 60 s (in 0.1 s
increments)/infinite
60 s
1 to 600 s (in 1 s
increments)/infinite
0.1 s
0.1 to 4 s (in 0.1 s
increments)
-
-
-
-
-
-
-
-
-
-
-
-
F3SG-SR/PG
User's Manual