The table below lists the data size and descriptions of the process data items.
Name
Power supply voltage
Sequence error information
Light level diagnosis information
(Channel 1)
Light level diagnosis information
(Channel 2)
Light level diagnosis information
(Channel 3)
Instantaneous Block Detection
Information (Channel 1)
Instantaneous Block Detection
Information (Channel 2)
Instantaneous Block Detection
Information (Channel 3)
Safety output status
Auxiliary output status
Mute A input status
Mute B input status
RESET/EDM/Override input status
Intelligent Tap Lockout information
Sensor or Intelligent Tap lockout
information
Reserved
*1. It is necessary to change the value in the setting of [Stable Light Threshold Adjustment] of the SD Manager 3.
Refer to 2-24. Stable Light Threshold Adjustment and 4-3-5-2. Stable Light Threshold Adjustment for more information on the
stable light threshold value.
*2. After the bit becomes 1 then normal blocking occurs, it becomes 0.
Data size
16 bits
Power supply voltage value for Receiver being supplied. (mV)
1 bit
1: Under muting sequence error state or interlock sequence error state
0: The others
1 bit
1: When one segment system of the F3SG-SR/PG or the primary sensor
is unblocked and light intensity is within a range from 100% to 170%
(factory default setting*1) of ON-threshold for 10 s or longer. *2
0: The others
1 bit
1: When the 1st secondary sensor in cascade connection is unblocked
and light intensity is within a range from 100% to 170% (factory default
setting*1) of ON-threshold for 10 s or longer. *2
0: The others
1 bit
1: When the 2nd secondary sensor in cascade connection is unblocked
and light intensity is within a range from 100% to 170% (factory default
setting*1) of ON-threshold for 10 s or longer. *2
0: The others
1 bit
1: When the Sensor system of one segment system of the F3SG-SR/PG
or the primary sensor stops accidentally due to instantaneous
blocking.
0: The others
1 bit
1: When the Sensor system of the 1st secondary sensor in cascade
connection stops accidentally due to instantaneous blocking.
0: The others
1 bit
1: When the Sensor system of the 2nd secondary sensor in cascade
connection stops accidentally due to instantaneous blocking.
0: The others
1 bit
1: ON, 0: OFF
1 bit
1: ON, 0: OFF
1 bit
1: ON, 0: OFF
1 bit
1: ON, 0: OFF
1 bit
1: ON, 0: OFF
1 bit
1: Intelligent Tap is in LOCKOUT state
0: The others
1 bit
1: Sensor or Intelligent Tap is in LOCKOUT state
0: The others
4 bytes
0
Setting with Intelligent Tap
Description
F3SG-SR/PG
User's Manual
E
179