Setting with Intelligent Tap
(6) Restart
<When operating the F3SG-SR with the Intelligent Tap not connected>
When completing the Teach-in setting, power off the F3SG-SR and remove the Intelligent Tap. Then
restart the F3SG-SR.
<When operating the F3SG-SR with the Intelligent Tap connected>
When completing the Teach-in setting, power off the F3SG-SR and set the DIP Switch Position 1 at
OFF (Unlock). Then restart the F3SG-SR.
There are two ways to restart.
• Power cycling
• Pressing and holding reset switch (for 1 s or longer): Set the DIP Switch Position 1 at OFF (Unlock).
(If restarting the F3SG-SR with the DIP Switch Position 1 set at ON (Lock), the configured zone will
be invalid. In this case, try the steps again from (4).)
After the restarting, the F3SG-SR waits for the Backup process of the settings. Perform the Backup
process. After the Backup process is complete, the power off the F3SG-SR and set the DIP Switch
Position 1 at ON (Lock). Check if the DIP Switch Positions 2 to 8 and other settings are configured as
intended, and then restart the F3SG-SR. After the F3SG-SR is restarted, the check if the Fixed
Blanking zone and other settings are properly configured.
Refer to 3-6-2. Performing Backup for more information on the Backup procedure.
F3SG-SR/PG
170