4.
After the instruction starts to output pulses, the number of output pulses that S
5.
S
sets the ramp-up or ramp down time with the unit of 1ms. The value is effective when the instruction is executed
3
for the first time. If the target frequency specified by S
time is reloaded for execution. But if the target frequency is modified when the output enters the ramp-down process,
the instruction ignores the change.
6.
D only allows Y0.0–Y0.11 as the pulse output devices. After the instruction is executed, its output function becomes
the high-speed output, and the general instruction output point control is invalid. It is suggested that you do not use
the general output function after using the high-speed output function in the program.
7.
The target output frequency S
graphic.
8.
The ratio of Duty-OFF Time and Duty-ON Time for the pulse output is 1:1.
9.
There is no limit to how many times you can use the instruction a program. But only one output instruction that uses
the same output point can be executed in the same scan cycle. When several high-speed pulse output instructions
start the same output point in the program, the PLC first performs the output based on the instruction that is executed
first.
10.
After the high-speed output instruction for one output point is enabled, other instructions that occupy the same output
point can not start until the high-speed output instruction in execution is disabled.
11.
When the high-speed output instruction is executed in an interrupt program or is not in the main program, it is
suggested that you use the instruction with the auto-reset function when the output is completed and the PLC updates
the output state in the END instruction.
12.
After the stop flag is set, PLC performs the ramp-down stop; or it immediately stops the output only after the start
instruction is executed a second time and outputs a full pulse.
13.
Refer to the PLSY instruction (API 2700) for an explanation of the high-speed output points and corresponding SM/SR.
14.
Refer to Example 3 from the PLSY instruction (API 2700) for programming in ST language.
is modified in the ramp-up process, the ramp up or ramp down
1
, number of output pulses S
1
Cha p ter 6 App l ied Ins truc tio ns
specifies cannot be changed.
2
and ramp up/down time S
2
3
are illustrated in the following
6 - 8 8 5
6_