Troubleshooting For As01Dnet Modules - Delta AS Series Programming Manual

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

A S S e r i e s P r o g r a m m i n g M a n u a l
7.3.7.3
ERROR LED Indicators Blinking Every 0.5 Seconds
Warning type error codes:
Error
Code
16#1500
Remote module communication timeout
16#1502
Incorrect parameters
16#1503
Extension module communication timeout
The actual arrangement of the extension
16#1505
module is not consistant with the
configurations.
Extension module communication
16#1604
timeout
7.3.7.4
ERROR LED Indicators Blinking Every 0.2 Seconds
This happens when the 24 VDC power supply for the remote module is not sufficient. Check the power supply. If the
power supply is normal, remove the extension module from the CPU module and then check if the SCM remote module
is out of order.
Error codes:
Error
Code
24VDC power supply is not sufficient and
16#1303
then recovered from low-voltage for less
than 10 ms.
7.3.8

Troubleshooting for AS01DNET Modules

_7
Refer to sections 7.4.9 and 7.4.10 for more details.
7 - 2 6
Description
Description
Solution
Check the network connection cable of the remote
modules.
Check the parameter in HWCONFIG. Download the
parameter again.
Make sure the module is properly connected to the CPU
module and turn the modules on again.
Check the actual arrangement and the configuraitons.
1. Make sure the module is properly connected to the
CPU module and turn the modules on again.
2. If the problem persists, contact the local authorized
distributors.
Solution
Check if the 24 V power supply to the module is normal.