AS Ser ies Pro gra mm in g M anu al
Bit number
5
4
3
2
1
0
13. If you stopped executing the instruction, the channel values will stop updating.
14. Refer to the following table for more details when any of the Error flag is ON.
_6
ErrCode
16#1400
16#1401
16#1402
16#1403
16#1404
16#1405
16#1406
16#1410
6-490
Status
Description
0: normal
Ring counter -
Overflow
1: abnormal
Ring counter -
0: normal
Underflow
1: abnormal
Linear counter
– the value
0: normal
exceeds the
1: abnormal
upper limit
Linear counter
– the value
0: normal
exceeds the
1: abnormal
lower limit
Linear counter
0: normal
- Overflow
1: abnormal
Linear counter
0: normal
- Underflow
1: abnormal
This function is NOT available for this module.
The value is invalid or out of range.
No response from the module. Communication timeout.
HWCONFIG configuration error. Instruction stops.
There is no such counting channel for the HC module.
Input interface not selected. Instruction stops.
Invalid value in Action
One of the counting channel of the HC module is executing counting. Other channels cannot
perform the same task at the same time.
Remarks
In HWCONFIG you can set the option to detect or not to detect.
(default: detection disabled)
31
Cause of the error: when either overflow (>2
(<-2
)
Ways to clear the error: use the DHCCNT instruction to
reset/preset or execute RESET by the Z phase.
Cause of the error: the value of the linear counter exceeds the
user-defined range
Ways to clear the error: when the value of the linear counter is
within the user-defined range
Note: when the counting value exceeds the upper or lower limit,
the value will keep as the value in upper/lower limit. After the
values return to the acceptable range, the counting continues.
Cause of the error: even if the value of the linear counter
exceeds the user-defined range, the hardware counter
− 1) or underflow (<-2
31
continues counting. But if the hardware counter counting is
either overflow (>2
stops. After clearing the error, the counting resumes.
Ways to clear the error: use the DHCCNT instruction to
reset/preset or execute RESET by the Z phase.
Description
− 1) or underflow
31
31
), the counting