[Pr. Pc19_Function Selection C-6 (*Cop6)] - Mitsubishi Electric MR-J5-G User Manual

Hide thumbs Also See for MR-J5-G:
Table of Contents

Advertisement

[Pr. PC19_Function selection C-6 (*COP6)]

Initial value
00000000h
[Pr. PC19.0_[AL. 099 Stroke limit warning] selection]
Initial value
0h
Enable or disable [AL. 099 Stroke limit warning].
When "Disabled" is selected, [AL. 099] does not occur while LSP (Forward rotation stroke end) or LSN (Reverse rotation
stroke end) is off, but the operation will be stopped with the stroke limit.
0: Enabled
1: Disabled
[Pr. PC19.4_Output open-phase detection selection]
Initial value
0h
Enable or disable the detection of output open-phase detection function.
0: Disabled
1: Enabled
[Pr. PC19.6_Output open phase - Judgment speed selection]
Initial value
0h
0: Servo motor speed
1: Speed command
When "0" (servo motor speed) is set, the value of the servo motor speed is used for the speed judgment of the output open-
phase detection.
When "1" (speed command) is set, the speed command value is used for the speed judgment of the output open-phase
detection.
In the torque mode, set "0" (servo motor speed). When "1" (speed command) is set, [AL. 139.2 Output open-phase error]
does not occur.
1 SERVO PARAMETER DETAILS
76
1.4 Extension setting servo parameters group ([Pr. PC_ _ ])
Setting range
Refer to the relevant detail No.
Setting range
Refer to the text
Setting range
Refer to the text
Setting range
Refer to the text
Setting method
Each axis
Ver.
A0
Ver.
A0
Ver.
A0
Ver.
Refer to the relevant detail No.