Group 13: PG function Parameters for Extension Card
Make sure that the extension card is installed on the AC motor drive correctly before using group 12
parameters. See Appendix B for details.
13.00

PG Input

Settings
The relationship between the motor rotation and PG input is illustrated below:
FWD
REV
PULSE
GENERATOR
13.01

PG Pulse Range

Settings
A Pulse Generator (PG) is used as a sensor that provides a feedback signal of the motor
speed. This parameter defines the number of pulses for each cycle of the PG control.
13.02

Motor Pole Number (Motor 0)

Settings
The pole number should be even (can't be odd).
13.03
Proportional Gain (P)
Settings
This parameter specifies proportional control and associated gain (P), and is used for speed
control with PG feedback.
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
0
Disable PG
1
Single phase
2
Forward/Counterclockwise rotation
3
Reverse/Clockwise rotation
PG
1 to 20000
2 to 10
0.0 to 10.0
Chapter 4 Parameters|
A phase leads B phase
A phase
CCW
B phase
13.00=2
B phase leads A phase
A phase
CW
B phase
13.00=3
A phase
CW
B phase
Factory Setting: 0
Unit: 1
Factory Setting: 600
Unit: 1
Factory Setting: 4
Unit: 0.01
Factory Setting: 1.0