This function is only for ACI signal.
AC motor drive action when the feedback signals (analog PID feedback) are abnormal
according to Pr.10.16.

Gain Over the PID Detection Value

10.10
Settings
This function is only for ACI signal.
This is the gain adjustment over the feedback detection value. Refer to PID control block
diagram in Pr.10.06 for detail.
10.11

Source of PID Set point

Settings
This parameter is used in conjunction with Pr.10.00 set 4 to input a set point in Hz.
10.12
PID Offset Level
Settings
10.13

Detection Time of PID Offset

Settings
This parameter is used to set detection of the offset between set point and feedback.
When the offset is higher than the setting of Pr.10.12 for a time exceeding the setting of
Pr.10.13, the AC motor drive will output a signal when Pr.03.00 ~ Pr.03.01 is set to 16.
10.14
Sleep/Wake Up Detection Time
Settings
10.15
Sleep Frequency
Settings
10.16

Wakeup Frequency

Settings
When the actual output frequency
the AC motor drive will be in sleep mode.
When the actual frequency command > Pr.10.16 and the time exceeds the setting of Pr.10.14,
the AC motor drive will restart.
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
0.0 to 10.0
0.00 to 600.0Hz
1.0 to 50.0%
0.1 to 300.0 sec
0.0 to 6550 sec
0.00 to 600.0 Hz
0.00 to 600.0 Hz
Pr.10.15 and the time exceeds the setting of Pr.10.14,
Chapter 4 Parameters|
Factory Setting: 1.0
Factory Setting: 0.00
Factory Setting: 10.0
Factory Setting: 5.0
Factory Setting: 0.0
Factory Setting: 0.00
Factory Setting: 0.00
Unit: 0.1
Unit: 0.01
Unit: 0.1
Unit: 0.1
Unit: 0.1
Unit: 0.01
Unit: 0.01
4-135