Chapter 4 Parameters|
Parameter
Explanation
Maximum Voltage
01.01
Frequency (Fbase)
(Motor 0)
Maximum Output
01.02
Voltage (Vmax)
(Motor 0)
Mid-Point Frequency
01.03
(Fmid) (Motor 0)
Mid-Point Voltage
01.04
(Vmid) (Motor 0)
Minimum Output
01.05
Frequency (Fmin)
(Motor 0)
Minimum Output
01.06
Voltage (Vmin)
(Motor 0)
Output Frequency
01.07
Upper Limit
Output Frequency
01.08
Lower Limit
01.09
Accel Time 1
01.10
Decel Time 1
01.11
Accel Time 2
01.12
Decel Time 2
01.13
Jog Acceleration
Time
01.14
Jog Deceleration
Time
01.15
Jog Frequency
Auto acceleration /
deceleration (refer
01.16
to Accel/Decel time
setting)
4-4
Settings
0.10 to 600.0 Hz
115V/230V series: 0.1V to 255.0V
460V series: 0.1V to 510.0V
0.10 to 600.0 Hz
115V/230V series: 0.1V to 255.0V
460V series: 0.1V to 510.0V
0.10 to 600.0 Hz
115V/230V series: 0.1V to 255.0V
460V series: 0.1V to 510.0V
0.1 to 120.0%
0.0 to100.0 %
0.1 to 600.0 / 0.01 to 600.0 sec
0.1 to 600.0 / 0.01 to 600.0 sec
0.1 to 600.0 / 0.01 to 600.0 sec
0.1 to 600.0 / 0.01 to 600.0 sec
0.1 to 600.0 / 0.01 to 600.0 sec
0.1 to 600.0 / 0.01 to 600.0 sec
0.10 Hz to Fmax (Pr.01.00) Hz
0: Linear Accel/Decel
1: Auto Accel, Linear Decel
2: Linear Accel, Auto Decel
3: Auto Accel/Decel (Set by load)
4: Auto Accel/Decel (set by Accel/Decel
Time setting)
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
Factory
Customer
Setting
60.00
220.0
440.0
1.50
10.0
20.0
1.50
10.0
20.0
110.0
0.0
10.0
10.0
10.0
10.0
1.0
1.0
6.00
0