4.4 Different Parameters for VFD*E*C Models

Software version for VFD*E*C is V1.00 for power board and V2.00 for control board.
: The parameter can be set during operation.

Group 0 User Parameters

Parameter
Explanation
00.02
Parameter Reset
Start-up Display
00.03
Selection
Content of Multi-
00.04
function Display
4-152
Settings
0: Parameter can be read/written
1: All parameters are read only
6: Clear PLC program (NOT for VFD*E*C
models)
9: All parameters are reset to factory settings
(50Hz, 230V/400V or 220V/380V depends on
Pr.00.12)
10: All parameters are reset to factory
settings (60Hz, 220V/440V)
0: Display the frequency command value
(Fxxx)
1: Display the actual output frequency (Hxxx)
2: Display the content of user-defined unit
(Uxxx)
3: Multifunction display, see Pr.00.04
4: FWD/REV command
5: PLCx (PLC selections: PLC0/PLC1/PLC2)
(NOT for VFD*E*C models)
0: Display the content of user-defined unit
(Uxxx)
1: Display the counter value (c)
2: Display PLC D1043 value (C) (NOT for
VFD*E*C models)
3: Display DC-BUS voltage (u)
4: Display output voltage (E)
5: Display PID analog feedback signal value
(b) (%)
6: Output power factor angle (n)
7: Display output power (P)
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
Factory
Customer
Setting
0
0
0

Hide quick links: