Chapter 2 Installation and Wiring|
The position of the control terminals
MI1 MI2 MI3 MI4 MI5 MI6
Terminal symbols and functions
Terminal
Terminal Function
Symbol
MI1
Forward-Stop command
MI2
Reverse-Stop command
MI3
Multi-function Input 3
MI4
Multi-function Input 4
MI5
Multi-function Input 5
MI6
Multi-function Input 6
+24V
DC Voltage Source
DCM
Digital Signal Common
Multi-function Relay output
RA
(N.O.) a
Multi-function Relay output
RB
(N.C.) b
RC
Multi-function Relay common
2-18
AFM MCM MO1
DCM
DCM 24V
ACM AVI ACI
Factory Settings (NPN mode)
ON: Connect to DCM
ON:
Run in MI1 direction
OFF:
Stop acc. to Stop Method
ON:
Run in MI2 direction
OFF:
Stop acc. to Stop Method
Refer to Pr.04.05 to Pr.04.08 for programming the
Multi-function Inputs.
ON: the activation current is 5.5mA.
OFF: leakage current tolerance is 10 μ A.
+24VDC, 20mA used for PNP mode.
Common for digital inputs and used for NPN
mode.
Resistive Load:
5A(N.O.)/3A(N.C.) 240VAC
5A(N.O.)/3A(N.C.) 24VDC
Inductive Load:
1.5A(N.O.)/0.5A(N.C.) 240VAC
1.5A(N.O.)/0.5A(N.C.) 24VDC
Refer to Pr.03.00 for programming
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11