Group 12: Analog Input/Output Parameters For Extension Card - Delta Electronics AC Motor Drive VFD-E User Manual

Vfd-e high performance/flexible options/micro type ac motor drives
Table of Contents

Advertisement

Group 12: Analog Input/Output Parameters for Extension Card

Parameter
Explanation
AI1 Function
12.00
Selection
AI1 Analog Signal
12.01
Mode
Min. AVI3 Input
12.02
Voltage
Min. AVI3 Scale
12.03
Percentage
Max. AVI3 Input
12.04
Voltage
Max. AVI3 Scale
12.05
Percentage
Min. ACI2 Input
12.06
Current
Min. ACI2 Scale
12.07
Percentage
Max. ACI2 Input
12.08
Current
Max. ACI2 Scale
12.09
Percentage
AI2 Function
12.10
Selection
AI2 Analog Signal
12.11
Mode
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
Settings
0: Disabled
1: Source of the 1st frequency
2: Source of the 2nd frequency
3: PID Set Point (PID enable)
4: Positive PID feedback
5: Negative PID feedback
0: ACI2 analog current (0.0 ~ 20.0mA)
1: AVI3 analog voltage (0.0 ~ 10.0V)
0.0 to 10.0V
0.0 to 100.0%
0.0 to 10.0V
0.0 to 100.0%
0.0 to 20.0mA
0.0 to 100.0%
0.0 to 20.0mA
0.0 to 100.0%
0: Disabled
1: Source of the 1st frequency
2: Source of the 2nd frequency
3: PID Set Point (PID enable)
4: Positive PID feedback
5: Negative PID feedback
0: ACI3 analog current (0.0 ~ 20.0mA)
1: AVI4 analog voltage (0.0 ~ 10.0V)
Chapter 4 Parameters|
Factory
Setting
0
1
0.0
0.0
10.0
100.0
4.0
0.0
20.0
100.0
0
1
Customer
4-29