Affecting Other Machines; High Harmonics At Power Side; Motor Temperature Rises - Delta Electronics AC Motor Drive VFD-E User Manual

Vfd-e high performance/flexible options/micro type ac motor drives
Table of Contents

Advertisement

Chapter 5 Troubleshooting|
4.
Store within a relative humidity range of 0% to 90% and non-condensing environment.
Use an air conditioner and/or exsiccator.

5.15 Affecting Other Machines

An AC motor drive may affect the operation of other machines due to many reasons. Some solutions
are:

High Harmonics at Power Side

High harmonics at power side during running can be improved by:
1.
Separate the power system: use a transformer for AC motor drive.
2.
Use a reactor at the power input terminal of the AC motor drive.
3.
If phase lead capacitors are used (never on the AC motor drive output!!), use serial
reactors to prevent damage to the capacitors damage from high harmonics.

Motor Temperature Rises

When the motor is a standard induction motor with fan, the cooling will be bad at low speeds,
causing the motor to overheat. Besides, high harmonics at the output increases copper and
core losses. The following measures should be used depending on load and operation
range.
1.
Use a motor with independent ventilation (forced external cooling) or increase the motor
rated power.
2.
Use a special inverter duty motor.
3.
Do NOT run at low speeds for long time.
5-10
serial reactor
phase lead capacitor
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents