Description Of Parameter Settings; Group 0: User Parameters; Rated Current Display Of The Ac Motor Drive; Parameter Reset - Delta Electronics AC Motor Drive VFD-E User Manual

Vfd-e high performance/flexible options/micro type ac motor drives
Table of Contents

Advertisement

4.3 Description of Parameter Settings

Group 0: User Parameters

00.00
Identity Code of the AC Motor Drive
Settings
00.01

Rated Current Display of the AC Motor Drive

Settings
Pr. 00.00 displays the identity code of the AC motor drive. The capacity, rated current, rated
voltage and the max. carrier frequency relate to the identity code. Users can use the following
table to check how the rated current, rated voltage and max. carrier frequency of the AC motor
drive correspond to the identity code.
Pr.00.01 displays the rated current of the AC motor drive. By reading this parameter the user
can check if the AC motor drive is correct.
kW
0.2
HP
0.25
Pr.00-00
Rated Output
1.6
Current (A)
Max. Carrier
Frequency
kW
0.4
HP
0.5
Pr.00-00
Rated Output
1.5
Current (A)
Max. Carrier
Frequency
00.02

Parameter Reset

Settings 0
1
6
9
10
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
Read Only
Read Only
0.4
0.75
0.5
1.0
0
2
2.5
4.2
0.75
1.5
1.0
2.0
3
5
2.5
4.2
Parameter can be read/written
All parameters are read-only
Clear PLC program (NOT for VFD*E*C models)
All parameters are reset to factory settings (50Hz, 230V/400V or
220V/380V depends on Pr.00.12)
All parameters are reset to factory settings (60Hz, 115V/220V/440V)
This parameter can be set during operation.
115V/230V Series
1.5
2.0
4
6
7.5
11.0
15kHz
460V Series
2.2
3.0
7
9
5.5
15kHz
Chapter 4 Parameters|
Factory setting: ##
Factory setting: #.#
2.2
3.7
3.0
5.0
8
10
17
3.7
5.5
5.0
7.5
11
13
8.5
13
Factory Setting: 0
5.5
7.5
7.5
10
12
14
25
33
7.5
11
10
15
15
17
18
24
4-37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents