Parameter
Explanation
Proportional Gain
10.02
(P)
10.03
Integral Time (I)
Derivative Control
10.04
(D)
Upper Bound for
10.05
Integral Control
Primary Delay Filter
10.06
Time
PID Output Freq
10.07
Limit
PID Feedback
10.08
Signal Detection
Time
Treatment of the
10.09
Erroneous PID
Feedback Signals
Gain Over the PID
10.10
Detection Value
Source of PID Set
10.11
point
10.12
PID Offset Level
Detection Time of
10.13
PID Offset
Sleep/Wake Up
10.14
Detection Time
10.15
Sleep Frequency
10.16
Wakeup Frequency
Minimum PID
10.17
Output Frequency
Selection

Group 11 Parameters for Extension Card

4-26
Settings
0.0 to 10.0
0.00 to 100.0 sec (0.00=disable)
0.00 to 1.00 sec
0 to 100%
0.0 to 2.5 sec
0 to 110%
0.0 to 3600 sec (0.0 disable)
0: Warn and RAMP to stop
1: Warn and COAST to stop
2: Warn and keep operation
0.0 to 10.0
0.00 to 600.0Hz
1.0 to 50.0%
0.1 to 300.0 sec
0.0 to 6550 sec
0.00 to 600.0 Hz
0.00 to 600.0 Hz
0: By PID control
1: By minimum output frequency (Pr.01.05)
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
Factory
Customer
Setting
1.0
1.00
0.00
100
0.0
100
60.0
0
1.0
0.00
10.0
5.0
0.0
0.00
0.00
0