Chapter 6 Fault Code Information and Maintenance|

6.1.2 Reset

There are three methods to reset the AC motor drive after solving the fault:
1.
Press
2.
Set external terminal to "RESET" (set one of Pr.04.05~Pr.04.08 to 05) and then set to be
ON.
3.
Send "RESET" command by communication.
NOTE
Make sure that RUN command or signal is OFF before executing RESET to prevent damage or
personal injury due to immediate operation.

6.2 Maintenance and Inspections

Modern AC motor drives are based on solid-state electronics technology. Preventive maintenance is
required to keep the AC motor drive in its optimal condition, and to ensure a long life. It is
recommended to have a qualified technician perform a check-up of the AC motor drive regularly.

Daily Inspection:

Basic check-up items to detect if there were any abnormalities during operation are:
1.
Whether the motors are operating as expected.
2.
Whether the installation environment is abnormal.
3.
Whether the cooling system is operating as expected.
4.
Whether any irregular vibration or sound occurred during operation.
5.
Whether the motors are overheating during operation.
6.
Always check the input voltage of the AC drive with a Voltmeter.

Periodic Inspection:

Before the check-up, always turn off the AC input power and remove the cover. Wait at least 10
minutes after all display lamps have gone out, and then confirm that the capacitors have fully
discharged by measuring the voltage between
6-6
key on keypad.
~
. It should be less than 25VDC.
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11