Using Multi-Step Speed Operation - YASKAWA Varispeed G7 Series Instruction Manual

General purpose inverter (advanced vector control)
Hide thumbs Also See for Varispeed G7 Series:
Table of Contents

Advertisement

Using Multi-Step Speed Operation

With Varispeed-G7 series Inverters, you can change the speed to a maximum of 17 steps, using 16 frequency
references, and one jog frequency reference.
The following example of a multi-function input terminal function shows a 9-step operation using multi-step
references 1 to 3 and jog frequency selection functions.
Related Constants
To switch frequency references, set multi-step speed references 1 to 3 and the jog reference selection in the
multi-function contact inputs. Setting examples are shown below.
Multi-function Contact Inputs (H1-01 to H1-10)
Constant
Terminal
Number
S5
H1-03
S6
H1-04
S9
H1-07
S7
H1-05
Combination of Multi-Function References and Multi-Function Contact Inputs
You can change the selected frequency reference by combining the ON/OFF status of S5 to S9 (multi-function
contact input terminals) to set multi-step speed references 1 to 3 and the jog frequency selection. The follow-
ing table shows the possible combinations.
TerminalS5
Multi-step
Speed
Speed Refer-
ence 1
1
OFF
2
ON
3
OFF
4
ON
5
OFF
6
ON
7
OFF
8
ON
9
* Terminal S7's jog frequency selection is given priority over multi-step speed references.
Set Value
(Factory Setting)
Multi-step speed reference 1 (Also used for master speed/auxiliary speed switching when
3
multi-function analog input H3-05 is set to 2 (auxiliary frequency reference 1).)
Multi-step speed reference 2 [Also used for auxiliary frequency reference 2 when multi-
4
function analog input H3-09 is set to 3 (auxiliary frequency reference 2).]
5
Multi-step speed reference 3
6
Jog frequency selection (given priority over multi-step speed reference)
TerminalS6
TerminalS9
TerminalS7
Multi-step
Multi-step
Jog Fre-
Speed Refer-
Speed Refer-
quency Selec-
ence 2
ence 3
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
ON
Details
Selected Frequency
tion
OFF
Frequency reference 1 d1-01, master speed frequency
OFF
Frequency reference 2 d1-02, auxiliary frequency 1
OFF
Frequency reference 3 d1-03, auxiliary frequency 2
OFF
Frequency reference 4 d1-04
OFF
Frequency reference 5 d1-05
OFF
Frequency reference 6 d1-06
OFF
Frequency reference 7 d1-07
OFF
Frequency reference 8 d1-08
*
Jog frequency d1-17
ON
Frequency Reference