E Motor Parameters; E1 V/F Pattern 1 - YASKAWA VS-616G5 Series Programming Manual

Hide thumbs Also See for VS-616G5 Series:
Table of Contents

Advertisement

ƒ By giving a stop command during torque control, operation changes to speed control automati-
cally, and the motor decelerates to stop. The torque limit during deceleration to stop becomes the
values set in the torque limit parameters (L7-01 to L7-04).
Note:
The control mode actually changes after the speed/torque control selection command changes
and after the reference delay timer (D5-06) elapses. The terminal 13 speed reference/speed
limit and the terminal 16 torque limit/torque reference are stored in the inverter until the time
set to D5-06 elapses.
E
Motor Parameters
E1
V/f Pattern
E1-01 Input Voltage
Setting Range:
Factory Default:
Sets the inverter input voltage in units of 1V.
E1-02 Motor Selection
Select between fan-cooled, blower-cooled and vector/inverter duty motor types with this parameter.
Setting
E1-03 V/f Pattern Selection
Choose a preset V/f pattern for operation in V/f modes only. It may be necessary to change the V/f pat-
tern when using a high-speed motor, or when special torque adjustment is required in the application.
Set values 0 to E:
F:
Preset V/f patterns are automatically scaled by the input voltage value set in parameter E1-01. Set the
V/f pattern according to the applications described in the table on the following page:
VS-616G5 Programming Manual
155 to 255V (230V class), 310 to 510V (460V class) 445 to 733 (575V class)
230V, 460V, 575V
<1110>
0
Fan-cooled motor characteristics (factory default)
1
Blower-cooled or TENV motor characteristics
This setting allows 120% motor current at and above 5.6 Hz
continuously, and allows 100% motor current at 0 Hz continu-
ously (w/ linear in between).
2
Vector/inverter duty motor
This setting allows 120% motor current at all frequencies.
preset V/f pattern can be selected
custom V/f pattern can be set (factory default)
Input Voltage
Motor Selection
Description
<1110>
V/f Selection
Section E: Motor Parameters
E1 V/F Pattern
Open Loop
Flux
V/f
V/f w/PG
Vector
Vector
Q
Q
Q
Q
<1110>
Q
Q
Q
Q
Q
Q
Q
Q
53

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents