Parameter Setting Error
on the digital operator, and the fault relay is not activated.
506
515
OPE11
FC/ On-Dly
Possible Cause(s):
Corrective Action:
Check the program settings and correct the errors.
506
515
CALL
Serial Com Call
Possible Cause(s):
proper baud rate or configuration.
Corrective Action:
Fault Codes
505
Carrier frequency data setting fault.
N/A
Upper limit (C6-01) >5KHz, and the lower limit
(C6-02) <= 5KHz.
Carrier frequency proportional gain (C6-03) > 6 and
(C6-01) < (C6-02).
Parameter setting incorrect.
505
Serial communication transmission error.
call
Communication has not yet been established.
Connection not made properly, user software not configured to the
Check all connections, verify all user side software configurations.
- Inverter can't run. The fault is displayed

PP.P5G5.03.Troubleshoot