Technical data for PDP

....................................................................................................................................................................................................................................
Specifications
Item
Power consumption,
Circuit breakers
Voltage range
(all components)
Power feeds
Ground
Dimensions (H x W x D)
....................................................................................................................................................................................................................................
3 - 1 8
The PDP has the following specifications:
Quantity / Size
Release 1.0 and 2.0:
max. 2700 W
68 A circuit breakers must be used in the External Battery
and Fuse Bay (BDFB)
63 A circuit breakers are part of the subracks.
Release 2.1:
max. 3500 W
Circuit breakers ≥ 100 A must be used in the External
Battery and Fuse Bay (BDFB)
100 A circuit breakers are part of the subracks.
-48 to -60 V battery voltages
(-40.5 V minimum, -72 V maximum)
3 power feeders (only 2 are necessary for one rack)
3 ground-connection points (only 2 are necessary for one rack)
70 mm [2.756"] x 482.6 mm [19"] x 60 mm [2.362"]
Figure 3-4 Layout
Lucent Technologies
Mechanical installation
365-374-074
Issue a, April 2002