Power Wiring (Pdp - Pi/100) - Lucent Technologies LambdaUnite MSS Installation Manual

Multiservice switch
Table of Contents

Advertisement

Power and ground cable installation

Power wiring (PDP - PI/100)

....................................................................................................................................................................................................................................
Before you begin
PI/100 cables
....................................................................................................................................................................................................................................
4 - 1 2
This section can be skipped, if PI units are used (see section
wiring (PDP - PI)"
Important! The PI/100 unit can only be used when the rack is
provided with 25mm
Important! The cables are prefabricated and mounted within the rack
frames. Each cable (cable for side A and cable for side B) supports
both subracks (upper and lower).
The following PI/100 cables should be used within ETSI-2 racks:
PI/100 cable, A-side — CC848850723
PI/100 cable, B-side — CC848850715.
The following PI/100 cables should be used within NEBS-2000 racks:
PI/100 cable, A-side — CC848850749
PI/100 cable, B-side — CC848850731.
Figure 4-7 PDP connection (PI/100 cables)
Ground (A+B)
+DC (rtn)
(A+B)
Legend:
4, 5
+DC (rtn)
Lucent Technologies
(4-7)).
2
power cables.
-DC
(A+B)
PI/100 cables (combined: yellow/green, red,
blue)
red
System cabling and final assembly
"Power
4A
5A
365-374-074
Issue a, April 2002