Nx Unit Mounting Settings; Introduction - Omron PROFINET NX-PNC202 User Manual

Machine automation controller coupler unit
Table of Contents

Advertisement

11 PROFINET Coupler Unit Functions

11-2 NX Unit Mounting Settings

This section describes the NX Unit mounting function when the disabled setting is used.

11-2-1 Introduction

The disabled setting is used to register NX Units that are not connected to the actual configuration but
will be added at a later time in the Unit configuration information as unmounted Units.
If you use this function, you do not have to modify the user program after the NX Units are added
because of the following reasons.
• IO memory area is reserved for these unmounted NX Units in the same way that it is reserved for
mounted NX Units.
• Unmounted NX Units are also assigned NX Unit numbers. This prevents the NX Unit numbers of
other NX Units in the same IO Device Terminal from changing when you change the setting of an NX
Unit from unmounted to mounted.
Current Unit
configuration
PROFINET
Coupler Unit
Unit configuration
information that is
Unit configuration
created
information
The Unit configuration information includes information on unmounted Units so that I/O memory area is
also reserved for them.
11 - 4
♯2
NX Unit
NX Units to add later
PROFINET
♯1
Coupler Unit
NX Unit
♯1
♯2
NX Unit
NX Unit
(Set as an
unmounted
Unit.)
♯3
♯7
NX Unit
NX Unit
♯4
♯5
♯6
NX Unit
NX Unit
NX Unit
♯3
♯4
♯5
NX Unit
NX Unit
NX Unit
NX Unit
(Set as an
unmounted
Unit.)
NX-series PROFINET Coupler Unit User's Manual (W623)
End Cover
♯8
NX Unit
♯6
♯7
♯8
NX Unit
NX Unit
(Set as an
unmounted
Unit.)

Advertisement

Table of Contents
loading

Table of Contents