6 Installation
Forced Ventilation by Fan at Top of Panel
Fan
Air filter
Forced Ventilation Method
Forced Air Circulation by Fan in Closed Panel
Fan
PROFINET
IO Device
PROFINET
IO Device
Forced Circulation Method
Room Cooling (Cooling the Entire Room Where the Control Panel Is Located)
Low Temperatures
The Profinet IO Device Terminal may not start normally if the temperature is below 0°C when the power
is turned ON.
Maintain an air temperature of at least approximately 5°C inside the panel, by implementing measures
such as installing a low-capacity space heater in the panel.
Alternatively, leave the Profinet IO Device Terminal power ON to keep the Profinet IO Device Terminal
warm.
6 - 24
PROFINET
IO Device
PROFINET
IO Device
Air conditioner
Control panel
Room Cooling
NX-series PROFINET Coupler Unit User's Manual (W623)