Event name
Unit Configuration Error, Too Many Units
Meaning
The number of connected NX Units exceeds the maximum value for the Communication Coupler Unit.
Source
Build-in Ethernet port
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
More than the maximum number
of NX Units is connected to the
Communication Coupler Unit.
Attached
None
information
Precautions/
None
Remarks
NX-series PROFINET Coupler Unit User's Manual (W623)
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Reduce the number of NX Units
that are connected to the maxi-
mum number or fewer.
12 Troubleshooting
Event code
24A00000 hex
Detection
Communica-
tions Coupler
timing
Unit
Cycle power to
Log category
the Communi-
cations Cou-
pler Unit or
restart the IO
Device Termi-
nal.
• Communications Coupler Unit, PROFINET Com-
munications
Ethernet communication stops.
• Communications Coupler Unit, NX Bus
IO refreshing for the NX Units in the IO Device Ter-
minal stops.
Messages cannot be sent to the NX Units in the IO
Device Terminal.
Name
---
Prevention
Configure the Unit within the maxi-
mum number of NX Units.
When power is
turned ON to
the Communi-
cations Cou-
pler Unit or the
IO Device Ter-
minal is
restarted
System
12
12 - 19