Omron PROFINET NX-PNC202 User Manual page 244

Machine automation controller coupler unit
Table of Contents

Advertisement

12 Troubleshooting
Event name
Unit Configuration Information Error
Meaning
An error occurred in the Unit configuration information in the Communications Coupler Unit.
Source
Build-in Ethernet port
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
The power supply to the Commu-
nications Coupler Unit was turned
OFF or Sysmac Studio communi-
cations were disconnected while
downloading the Unit configura-
tion information.
Attached
None
information
Precautions/
None
Remarks
12 - 20
Source details
Recovery
Minor fault
Continues.
Operation
Data type
---
Correction
Clear all of memory in the Com-
munication Coupler Unit, and then
download the Unit configuration
information again.
Event code
35000000 hex
Communica-
Detection
tions Coupler
timing
Unit
Log category
Cycle power to
the Communi-
cations Cou-
pler Unit or
restart the IO
Device Termi-
nal.
• Communications Coupler Unit, PROFINET Com-
munications
Ethernet communication stops.
• Communications Coupler Unit, NX Bus
IO refreshing for the NX Units in the IO Device Ter-
minal stops.
Messages cannot be sent to the NX Units in the IO
Device Terminal.
Name
---
Prevention
Do not turn OFF the power supply
to the Communications Coupler
Unit or disconnect Sysmac Studio
communications while download-
ing the Unit configuration informa-
tion.
NX-series PROFINET Coupler Unit User's Manual (W623)
When power is
turned ON to
the Communi-
cations Cou-
pler Unit or the
IO Device Ter-
minal is
restarted
System