Omron PROFINET NX-PNC202 User Manual page 123

Machine automation controller coupler unit
Table of Contents

Advertisement

Signal
cables
(group A)
Signal cables
Power supply cables
Partitioning Methods for Signal and Power Supply Cables
• To avoid overheating the conduits when using conduits for wiring, do not place wires for a single
circuit in separate conduits.
Power supply
Power supply
Power supply
Parallel Wiring (Single Phase)
• Power cables and signal cables adversely affect each other. Do not wire them in parallel.
• Noise induction may occur if the Profinet IO Device Terminal is installed in a panel that includes
high-voltage devices. Whenever possible, wire and install them separately.
• Either install the Profinet IO Device Terminal a minimum of 200 mm away from high-voltage lines
or power lines, or place the high-voltage lines or power lines in metal tubing and completely
ground the metal tubing to 100 Ω or less.
NX-series PROFINET Coupler Unit User's Manual (W623)
Signal
Signal
cables
cables
(group C)
(group B)
Signal cables
(a)
(c)
NG
Conduits
Incorrect
Conduits
OK
Correct
Conduits
OK
Correct
Partition
Power
supply
cables
(b)
Signal cables
Power supply cables
(d)
Load
Load
Load
6 Installation
6
6 - 29