Omron PROFINET NX-PNC202 User Manual page 237

Machine automation controller coupler unit
Table of Contents

Advertisement

Event
Event code
name
84C50000
NX Unit
hex
Startup
Error
350E0000
NX Bus
hex
Cycle Delay
Detected
80220000
NX Mes-
hex
sage Com-
munications
Error
90400000
Event Log
hex
Cleared
90420000
Restart
hex
Executed
90430000
Memory All
hex
Cleared
NX-series PROFINET Coupler Unit User's Manual (W623)
Meaning
Assumed cause
Starting an NX
• A startup error occurred in
Unit failed.
an NX Unit.
Exceeding the
• The NX bus cycle was
NX bus cycle was
exceeded.
detected.
An error was
For the NX bus of CPU Units
detected in mes-
• The message communica-
sage communi-
tions load is high.
cations and the
For Communications Coupler
message frame
Units
was discarded.
• The message communica-
tions load is high.
• The communications cable
is disconnected or broken.
• Message communications
were cutoff in communica-
tions.
The event log
• The event log was cleared
was cleared.
by the user.
A restart was
• A restart command was
executed.
received.
The Unit settings
• The Clear All Memory oper-
were cleared.
ation was executed.
12 Troubleshooting
Level
Maj Prt Min Obs Info
Reference
P. 12-27
P. 12-28
P. 12-29
12
P. 12-30
P. 12-30
P. 12-31
12 - 13

Advertisement

Table of Contents
loading

Table of Contents