Event name
Unit Configuration Verification Error
Meaning
There is an inconsistency between the Unit configuration information in the Communication Coupler Unit
and the Units that are actually connected. Or, the Unit configuration was changed during operation while the
Unit configuration information was not set in the Communication Coupler Unit.
Source
Build-in Ethernet port
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
NX-series PROFINET Coupler Unit User's Manual (W623)
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
12 Troubleshooting
Event code
35010000 hex
Communica-
Detection
tions Coupler
timing
Unit
Cycle power to
Log category
the Communi-
cations Cou-
pler Unit or
restart the IO
Device Termi-
nal.
When Fail-soft Operation Is Set to Fail-soft and
Fail-soft Operation Is Possible
• Communications Coupler Unit, NX Bus
IO refreshing for the NX Units that have a verifica-
tion error in the IO Device Terminal stops.
Messages cannot be sent to the NX Units that
have a verification error in the IO Device Terminal.
When Fail-soft Operation Is Set to Fail-soft and
Fail-soft Operation Is Not Possible
The operation is the same as when fail-soft opera-
tion is set to Stop.
When Fail-soft Operation Is Set to Stop
• Communications Coupler Unit, PROFINET Com-
munications
Ethernet communications stops.
• Communications Coupler Unit, NX Bus
IO refreshing for the NX Units in the IO Device Ter-
minal stops.
Messages cannot be sent to the NX Units in the IO
Device Terminal.
Name
---
When power is
turned ON to
the Communi-
cations Cou-
pler Unit, when
the IO Device
Terminal is
restarted, or
during NX bus
communica-
tions
System
12
12 - 21