9 Setting Up the PROFINET Coupler Unit
9-2-5

Sysmac Studio Functions Used as Required

You can use the following functions on the Sysmac Studio.
• Getting NX Unit serial numbers
• Comparing and merging with actual Unit configuration of the IO Device Terminal
• Exporting/importing NX Unit settings
• Uploading IO Device Terminal settings through the USB port on the PROFINET Coupler Unit
• Adding additional Coupler Units
Comparing and Merging with Actual Unit Configuration of the IO
Device Terminal
You can compare the Unit configuration information in an IO Device Terminal that was created offline
with the actual Unit configuration. You can also use this command to merge a configuration that was
created offline with the actual configuration.
1
Go online, right-click anywhere in the Edit IO Device Terminal Configuration Tab Page, and
select Compare and Merge with Actual Unit Configuration.
The actual Unit configuration is read and compared with the Unit configuration on the Sysmac
Studio.The results are displayed in the Compare and Merge with Actual Unit Configuration Dia-
log Box.
2
To merge with actual Unit configuration, click the Apply Actual Unit Configuration button.
The configuration information on the Sysmac Studio will now match the actual Unit configura-
tion.
3
Click the OK button.
The display returns to the Edit IO Device Terminal Configuration Tab Page.
Precautions for Correct Use
You can read only the Unit configuration in the IO Device Terminal by comparing and merging
with the actual Unit configuration. You cannot read the IO allocation information, Unit operation
settings, and Unit application data.