Omron PROFINET NX-PNC202 User Manual page 162

Machine automation controller coupler unit
Table of Contents

Advertisement

9 Setting Up the PROFINET Coupler Unit
Setting
Device name
Model name
Product name
Unit version
NX Unit Number
NX Unit Mounting
Setting
Serial Number
Supply
Power/Available
Power [W]
Unit width [mm]
Unit operation set-
tings
Number of mounted
Units
NX Unit Connection
Time (s)
Serial Number
Check Method
*1. If this setting is set to Setting = Actual device and you replace an NX Unit in the IO Device Terminal, a Unit
Configuration Verification Error will occur. A Unit Configuration Verification Error will also occur if you swap the
mounting position of two Units of the same model. If it becomes necessary to replace an NX Unit, or swap the
mounting positions of two Units of the same model while this setting is set to Setting = Actual device, you must
correct the Unit configuration information and download it to the PROFINET Coupler Unit. Set this parameter
to Setting = Actual device if strict management of the equipment configuration is required.
9 - 6
Settable
This is the name of the PROFINET Coupler Unit.
Use the PROFINET Configuration Edit Tab Page to
change this setting.
This is the model of the PROFINET Coupler Unit.
This is the product name.
This is the Unit version of the PROFINET Coupler Unit.
This number represents the logical position of the
PROFINET Coupler Unit.
This setting enables or disables the mounting of an NX
Unit. You cannot directly edit these settings in the
PROFINET Coupler Unit.
This is the serial number of the PROFINET Coupler
Unit. You can get the serial number to set the serial
number of the actual PROFINET Coupler Unit.
The power that is currently drawn by the NX Units and
the maximum available power supply capacity are
given.
This is the width of the PROFINET Coupler Unit.
Yes
These are the Unit operation settings for the PROF-
INET Coupler Unit. Click the Edit Unit Operation Set-
tings button to edit these settings.
This is the number of mounted NX Units.
Yes
This is the wait time for the NX Units to connect to the
IO Device Terminal.
Yes
Set this setting to Setting = Actual device to compare
the serial numbers of the NX Units at these times: when
the power is turned ON and after the PROFINET Cou-
pler Unit is restarted. The serial numbers of the NX
Units saved in the Unit configuration information are
compared with the actual serial numbers of the NX
*1
Units.
If differences are found, a Unit Configuration Verifica-
tion Error will occur.
Description
NX-series PROFINET Coupler Unit User's Manual (W623)
Data
Default
range
---
E *** (* is a serial
number from
001).
The default value
is automatically
generated based
on the node
address.
---
The model num-
ber of the PROF-
INET Coupler
Unit is shown.
---
PROFINET Cou-
pler Unit.
---
---
---
0
---
---
---
---
---
-/10.00
---
46
---
Refer to 9-2-3
Unit Operation
Settings on page
9-10.
---
---
3 to 200 s
3 s
No check.
No check.
Setting =
Actual
device

Advertisement

Table of Contents
loading

Table of Contents