 Error Descriptions
Event name
Bus Controller Error
Meaning
An internal bus error occurred.
Source
Build-in Ethernet port
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
A Unit failed or an IO communica-
tions error occurred between the
Communication Coupler Unit and
the NX Unit.
Attached
None
information
Precautions/
None
Remarks
NX-series PROFINET Coupler Unit User's Manual (W623)
Source details
Minor fault
Recovery
Operation
Continues.
Data type
---
Correction
Mount the NX Units and End
Cover securely and secure them
with End Plates.
Cycle the power supply to the
Communication Coupler Unit.
If the error occurs again even after
you make the above correction,
replace the Communication Cou-
pler Unit.
12 Troubleshooting
Event code
00210000 hex
Detection
Communica-
timing
tions Coupler
Unit
Cycle the power
Log category
supply to the
Communica-
tions Coupler
Unit
IO refreshing for the NX Units in the IO Device Ter-
minal stops.
Name
---
Prevention
None
When power is
turned ON to
the Communi-
cations Cou-
pler Unit or
during NX bus
communica-
tions
System
12
12 - 15