5 DATA LINK PROCESSING TIME
5.3.3 Master station
5 - 21
intelligent device station
(1) Master station
This indicates the time from the moment an instruction is issued by the master
station and a response from an intelligent device station is received.
[Expression]
[Maximum value]
(a) RIRD instruction
OT + LS
[BC + {(read points + 16)/16}
OT: QCPU (Q mode) dedicated instruction processing time
QnCPU : 1 [ms]
QnHCPU : 0.5 [ms]
LS: Link scan time (see Section 5.1)
BC: Constant
Transmission rate
1: Round up below the decimal point
(Example) When the PLC CPU type is Q06HCPU, the transmission rate is
10 Mbps, the link scan time is 5 ms and the read points are 20 words.
OT + LS
= 0.5 + 5
= 0.5 + 5
= 76.505
= 76.5 [ms]
(b) RIWT instruction
OT + LS × [BC + {(write points + 16)/72}
OT: QCPU (Q mode) dedicated instruction processing time
QnCPU : 1 [ms]
QnHCPU : 0.5 [ms]
LS: Link scan time (see Section 5.1)
BC: Constant
Transmission rate
1: Round up below the decimal point
(Example) When the PLC CPU type is Q06HCPU, the transmission rate is
10 Mbps, the link scan time is 5 ms and the write points are 20 words.
OT + LS
= 0.5 + 5
= 0.5 + 5
= 66.15
= 66.2 [ms]
intelligent device station
156 kbps 625 kbps 2.5 Mbps 5 Mbps
BC
6
[BC + {(read points + 16)/16}
[12 + {(20 + 16)/16}
[12 + {3
1.067}]
156 kbps 625 kbps 2.5 Mbps 5 Mbps
BC
6
[BC + {(write points + 16)/72}
[12 + {(20 + 16)/72}
[12 + {1
1.13}]
MELSEC-Q
1
1.067] [ms]
7
9
11
1
1.067] [ms]
1
1.067]
1
1.13] [ms]
7
9
11
1
1.13] [ms]
1
1.13]
10 Mbps
12
10 Mbps
12
5 - 21

Advertisement

Table of Contents
loading