8 PROGRAMMING
Number
Name
Forced master
SW005D
switching instruction
(65D
)
H
result
Remote device station
SW005F
initialization procedure
(65F
)
registration instruction
H
result
SW060
Mode setting status
(660
)
H
SW0061
Host station number
(661
)
H
SW0062
Module operating
(662
)
status
H
SW0064
No. of retries
(664
)
information
H
SW0065
No. of automatic
(665
)
return stations
H
SW0066
Delay timer
(666
)
information
H
SW0067
Parameter information
(667
)
H
SW0068
Host parameter status
(668
)
H
SW0069
4
Loading status
(669
)
H
1: Can be used for the master station only.
2: Can be used for the standby master station only.
4: This register checks and stores the status only at link startup.
8 - 24
Table 8.4 Link special register list (3/7)
Description
Stores the execution result of the forced master switching instruction
with SB000C.
0
: Normal
Other than 0: Stores the error code (see Section 13.3).
Stores the execution result of the initialization procedure registration
instruction with SB000B.
0
: Normal
Other than 0: Stores the error code (see Section 13.3).
Stores the mode setting status.
0: Online (with automatic return)
2: Offline
3: Line test 1
4: Line test 2
6: Hardware test
Stores the station number of the host that is currently in operation.
0
: Master station
1 to 64: Local station
Stores the operation setting status of the module.
b15
b6 b5 b4 b3 b2 b1 b0
0
to
0
0
0
Indicates the retry count setting information when there is an error
response.
1 to 7 (times)
Indicates the setting information for the number of automatic return
stations during one link scan.
1 to 10 (stations)
Indicates the setting information for the scan interval delay time.
0 to 100 (50 µ s)
Stores the parameter information area to be used.
0
: CPU built-in parameters
H
3
: Dedicated instruction (parameter setting with the RLPASET
H
instruction and data link startup.)
D
: Default parameters (automatically starts CC-Link)
H
Stores the parameter setting status.
0
: Normal
Other than 0: Stores the error code (see Section 13.3).
Stores the duplicate station number status and parameter matching of
each station.
0
: Normal
Other than 0: Stores the error code (see Section 13.3).
Details are stored in SW0098 to 9B and SW009C to
9F.
0
Station type
0: Master station/local station
1: Standby master station
Input status from the data
link faulty station
0: Clear
1: Hold
Number of occupied stations
0: 1 station
1: 4 stations
MELSEC-Q
Availability
(
: Available,
: Not available)
Online
Master station
Local station
2
1
Offline
8 - 24