8 PROGRAMMING

8.2.2 Details of the I/O signals

8 - 4
The following explains the on/off timings and conditions of the I/O signals shown in
Table 8.1:
(1) Module error: Xn0
This signal indicates whether the module is normal or faulty.
OFF: Module normal
ON : Module error
Module error
(Xn0)
Module ready
(XnF)
(2) Host data link status: Xn1
This signal indicates the data link status of the host station.
OFF: Data link is stopped
ON : Data linking in progress
(3) Other station data link status: Xn3
This signal indicates the data link status of other stations (remote, local,
intelligent device and standby master stations).
The SB0080 signal has the same contents.
OFF: All stations normal
ON : There is a faulty station (the faulty station status is stored in SW0080 to
SW0083)
(4) Module ready: XnF
This signal indicates whether the module is ready to operate.
(a) When the module reaches ready-to-operate status, this signal turns ON
automatically.
(b) This signal turns OFF when either of the following conditions occurs:
1) When an error is detected in the switch setting status for the module
2) When the module error signal (Xn0) turns ON
Module ready
(XnF)
Module error
(Xn0)
Power ON