7 PROCEDURE BEFORE STARTING THE DATA LINK
Number
Name
3)
Transmission rate/mode setting
switch
MODE
4)
Terminal block
NC
NC
DA
SLD
DB
(FG)
DG
7 - 6
Set the transmission rate and operating conditions for the module
(settings at time of shipment: 0)
Number
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Connect the CC-Link dedicated cable for data linking.
For the connection method, see Section 7.5.
Terminals SLD and FG are connected inside the module.
Since a 2-piece type terminal block is used, the module can be replaced
without disconnecting the signal line to the terminal block.
(Replace the module after turning its power OFF.)
POINT
The settings of the station number setting switch and the transmission rate/mode
setting switch become valid when the module power is turned from OFF to ON or
the PLC CPU is reset. Thus, if the settings were changed while the module power
was ON, turn the module power from OFF to ON or reset the PLC CPU again.
Description
Transmission rate settings
Transmission rate 156 kbps
Transmission rate 625 kbps
Transmission rate 2.5 Mbps
Transmission rate 5 Mbps
Transmission rate 10 Mbps
Transmission rate 156 kbps
Transmission rate 625 kbps
Transmission rate 2.5 Mbps
Transmission rate 5 Mbps
Transmission rate 10 Mbps
Transmission rate 156 kbps
Transmission rate 625 kbps
Transmission rate 2.5 Mbps
Transmission rate 5 Mbps
Transmission rate 10 Mbps
Setting not allowed
MELSEC-Q
Mode
Online
(see Section 7.7.2)
Line test (see Section 7.8)
When the station number setting
switch is set to 0: Line test 1
When the station number setting
switch is set to 1 to 64: Line test 2
Hardware test
(see Section 7.4)
7 - 6