4 FUNCTIONS
PLC CPU
X
PLC CPU
Y
DANGER
4 - 4
[Remote input]
2) The input status of a remote I/O station is stored automatically (for each
link scan) in the master station's "remote input RX" buffer memory.
3) The input status stored in the "remote input RX" buffer memory is
stored in the CPU device set with the automatic refresh parameters.
Master station
Remote input RX
RX0F to RX00
3)
RX1F to RX10
RX2F to RX20
RX3F to RX30
RX4F to RX40
to
RX7FF to RX7F0
[Remote output]
4) The on/off data of the CPU device set with the automatic refresh
parameters is stored in the "remote output RY" buffer memory.
5) The output status stored in the "remote output RY" buffer memory is
output automatically (for each link scan) to remote I/O stations.
Master station
Remote output RY
RY0F to RY00
RY1F to RY10
RY2F to RY20
RY3F to RY30
RY4F to RY40
4)
RY5F to RY50
RY6F to RY60
RY7F to RY70
RY8F to RY80
to
RY7FF to RY7F0
• When setting the automatic refresh parameters, be sure to specify "Y" for the
remote output RY refresh device. If any value other than "Y" (e.g. M or L) is
specified when the CPU stops, the status of the device before the stop is retained
as is. For the method to stop a data link, see Section 4.4.10.
Remote I/O station
(Station number 1:
occupies 1 station)
2)
X0F to X00
2)
16-point module
Remote I/O station
(Station number 3:
occupies 1 station)
5)
Y0F to Y00
5)
16-point module
MELSEC-Q
Remote I/O station
(Station number 2:
occupies 1 station)
X0F to X00
X1F to X10
32-point module
Remote I/O station
(Station number 4:
occupies 1 station)
Y0F to Y00
Y1F to Y10
32-point module
4 - 4