8 PROGRAMMING
Number
Name
SB0066
(5E6
, b6)
H
Number of host
occupied stations
4
SB0067
(5E6
, b7)
H
SB006A
Switch setting status
(5E6
, b10)
H
SB006D
Parameter setting
(5E6
, b13)
status
H
SB006E
Host station operation
(5E6
, b14)
status
H
SB0070
Master station
(5E7
, b0)
information
H
SB0071
Standby master
(5E7
, b1)
station information
H
SB0072
Scan mode setting
(5E7
, b2)
information
H
Operation
SB0073
specification when
(5E7
, b3)
H
CPU is down status
SB0074
Reserved station
(5E7
, b4)
specified status
H
SB0075
Error invalid station
(5E7
, b5)
specified status
H
Temporary error
SB0076
invalid station setting
(5E7
, b6)
H
information
SB0077
Parameter receive
(5E7
, b7)
status
H
SB0078
Host station switch
(5E7
, b8)
change detection
H
Master station return
SB0079
specification
(5E7
, b9)
H
information
4: For QJ61BT11 of the function version A, it is always OFF.
8 - 20
Table 8.3 Link special relay list (4/5)
Description
Indicates the setting status of host occupied stations.
Number of
occupied station
1 station
2 stations
3 stations
4 stations
Indicates the switch setting status.
OFF: Normal
ON : Setting error exists (the error code is stored in SW006A)
Indicates the parameter setting status.
OFF: Normal
ON : Setting error exists (the error code is stored in SW0068)
Indicates the host data link operation status.
OFF: Being executed
ON : Not executed
Indicates the data link status.
OFF: Data link control by the master station
ON : Data link control by the standby master station
Indicates whether or not a standby master station is present.
OFF: Not present
ON : Present
Indicates the scan mode setting information.
OFF: Asynchronous mode
ON : Synchronous mode
Indicates the operation specification status using a parameter when
the CPU is down.
OFF: Stop
ON : Continue
Indicates the reserved station specification status using a parameter.
OFF: No specification
ON : Specification exists (information is stored in SW0074 to
SW0077)
Indicates the error invalid station specification status using a
parameter.
OFF: No specification
ON : Specification exists (information is stored in SW0078 to
SW007B)
Indicates whether there is a temporary error invalid station setting.
OFF: No setting
ON : Setting exists (information is stored in SW007C to SW007F)
Indicates the parameter receive status from the master station.
OFF: Reception complete
ON : Reception not complete
Detects changes to the host setting switch during data linking.
OFF: No changes detected
ON : Changes detected
Indicates whether the "Type" setting of the network parameters is set
to "Master station" or "Master station (Duplex function)."
OFF: Master station
ON : Master station (Duplex function)
SB0066
SB0067
OFF
OFF
OFF
ON
ON
ON
ON
OFF
MELSEC-Q
Availability
(
: Available,
: Not available)
Online
Master station
Local station
Offline
8 - 20