13 TROUBLESHOOTING
Error code
Error details
(hexadecimal)
Loading/parameter
B30A
compatibility error
Loading/parameter
B30B
compatibility error
Standby master station
B30C
specification error
B30D
Initial status
Temporary error invalid station
B30F
specification error
Forced master station switching
B315
error
Network startup setting mode
B317
error
Station number switch setting
B381
error
B383
Baud rate setting error
Station number setting error
B384
(parameter)
Total number of stations error
B385
(parameter)
Number of occupied stations
B386
setting error (parameter)
B387
Use prohibited area write error
Station type setting error
B388
(parameter)
B389
Use prohibited area write error
Remote device station setting
B38B
error (parameter)
13 - 11
Table 13.1 Error code list (2/5)
Cause of error occurrence (details)
The station types of the module are
different from parameter settings.
Example)
Connected
Parameter
module
setting
Remote
Remote I/O
device
Remote I/O
Intelligent
Remote
device
device
The contents of the installation status
and network parameters do not match.
Master station switching was instructed
to a station other than the standby
master station.
Temporary error invalid station
specification and line test requests were
issued before starting the link.
A temporary error invalid station was
specified while the data link is being
performed upon automatic CC-Link
startup.
Forced master switching (SB000C) was
instructed again while the master station
was being switched to the standby
master station.
The RLPASET instruction was executed
for a module whose parameters have
been set by GX Developer.
The parameter setting was changed
without turning the power supply to the
PLC system off and back on, or resetting
the PLC CPU.
The station number switch was outside of
the setting range.
The baud rate setting was outside of the
setting range.
The station number (including the
number of occupied stations) of the
station information parameters was set to
"other than 1
to 40
."
H
H
The total number of occupied stations set
with the station information parameter
exceeded 64.
The number of all occupied stations in
the station information parameter was set
to "0".
Write operation was performed to a use
prohibited area (not used) in the buffer
memory.
The station type in the station information
parameter was set to "other than 0 to 2".
Write operation was performed to a use
prohibited area (not used) in the buffer
memory.
The number of remote device stations
was set to "43 stations or more" with the
station information parameter.
Corrective action
Set the correct parameters.
Set the contents of the
installation status and network
parameters to match.
Specify the station number that
corresponds to the standby
master station.
Issue the requests after the
data link is started.
Specify a temporary error
invalid station while the data
link is performed with
parameters set using GX
Developer or the dedicated
instruction.
Check ON/OFF of Forced
master switching (SB000C).
Use the RLPASET instruction
according to the procedure
below.
1. Clear the settings of the
network parameters and
refresh parameters of the
target module using GX
Developer.
2. Set the type of I/O
assignment setting in GX
Developer to "intelli."
3. Set switch 4 of the intelligent
function module switch
setting in GX Developer to
0100
.
H
4. Turn the power supply to the
PLC system off and back on,
or reset the PLC CPU.
Set the station number switch
within the setting range.
Set the baud rate setting within
the setting range.
Set within the range of "1
to
H
40
".
H
Set a parameter value of 64 or
less.
Set the occupied station
number to a value between "1
and 4".
Do not write to any of the use
prohibited areas (not used) in
the buffer memory.
Set to a value between "0 and
2".
Do not write to any of the use
prohibited areas (not used) in
the buffer memory.
Set the remote device station to
"42 stations or less" with the
station information parameter.
MELSEC-Q
Detectability
Master station
Local station
13 - 11