5 DATA LINK PROCESSING TIME
5 - 23
KM2, KM3 : Constant
1) When QJ61BT11 is mounted on main base unit
CPU type
Q00JCPU
Q00CPU
Q01CPU
Q02CPU
Q02HCPU, Q06HCPU, Q12HCPU, Q25HCPU, Q12PHCPU, Q25PHCPU
2) When QJ61BT11 is mounted on extension base unit
CPU type
Q00JCPU
Q00CPU
Q01CPU
Q02CPU
Q02HCPU, Q06HCPU, Q12HCPU, Q25HCPU, Q12PHCPU, Q25PHCPU
(Example) When the PLC CPU type is the Q06HCPU, the QJ61BT11 is mounted
on the main base and used as the master station, and 2048 points of
RX, 2048 points of RY, 256 points of RWw, 256 points of RWr, 512
points of SB and 512 points of SW are refreshed besides the file
register.
KM1 + KM2
16)} / 16]
= 0.16 + 0.00043
(512
16)} / 16]
= 0.16 + 0.00043
= 0.16 + 0.00043
= 0.72416
= 0.72 [ms]
[{RX + RY + SB + (RWw
[{2048 + 2048 + 512 + (256
[{2048 + 2048 + 512 + 4096 + 4096 + 8192} / 16]
20992 / 16
MELSEC-Q
Constant
KM2
KM3
-3
( 10
)
( 10
0.91
0.83
0.79
0.48
0.32
0.43
0.14
Constant
KM2
KM3
-3
( 10
)
( 10
1.62
1.57
1.55
1.02
0.08
0.98
0.06
16) + (RWr
16) + (SW
16) + (256
16) +
5 - 23
-3
)
-3
)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qj61bt11

Table of Contents