6 PARAMETER SETTINGS
Refresh of SB/SW
Parameter setting
RLPASET instruction
· Control data
· Slave station setting data
63
· Reserved station specification data
79
· Error invalid station specification data
92
· Send, receive and automatic refresh buffer assignment data
108
· Parameter registration (data link startup)
135
Processing at completion of the RLPASET instruction
167
Parameter setting change
Parameter
change instruction
191
6 - 18
(2) Program example
MELSEC-Q
SB0040 to SB01FF are read
to SB0040 to SB01FF.
SW0040 to SW01FF are read
to SW0040 to SW01FF.
Instruct to set parameters.
Clear complete status.
All setting data: Valid
Number of connected modules
involved in communication: 3
Number of retries: 3 times
Number of automatic return
modules: 1 module
Operation specification when
CPU is down: stop
Scan mode specification:
Asynchronous
Delay time setting: 0
First:
Local station, occupies
1 station, station
number 1
Second:
Remote I/O station,
occupies 1 station,
station number 2
Third:
Remote I/O station,
occupies 1 station,
station number 3
Reserved station specification:
station number 3
Error invalid station specification:
station number 2
First (station number 1) local station
Send buffer: 64
First (station number 1) local station
Receive buffer: 64
First (station number 1) local station
Automatic refresh buffer: 0
Dedicated instruction (RLRASET)
Turn the parameter setting
instruction off.
Instruct to refresh at normal
completion of the RLPASET
instruction.
Instruct to start the control
program at normal completion
of the RLPASET instruction.
Performs abnormal
completion processing
Instruct to stop data link.
H
H
H
6 - 18