5 DATA LINK PROCESSING TIME
5
5 - 2
TR: Transient processing time (only when a transient request is made)
When there is a transient request from the master station
180
BT
When there is a transient request from the local station
40.8
BT
(Example) Using the following system configuration when the transmission rate is
10 Mbps (assuming that there is no faulty station or transient
transmission.)
Station
number 1
number 2
1
Master
Remote
station
I/O station
device station
1: (occupies 1 station)
BT = 0.8
ST = 2300
NI = 12
16
1) 800 + (12
NW = 11
16
2) 900 + (3
N = 5
3) 1200 + (8
ni = 12
A = 12, B = 3, C = 11
nw = 10
LS = 0.8 {27 + (16
4.8) + (16
2300
= 2748.8 [µ s]
= 2.75 [ms]
number of transient transmission stations
Station
Station
number 4
2
Remote
Intelligent
device station
2: (occupies 2 stations)
3: (occupies 4 stations)
15) = 980
50) = 1050
100) = 2300
9.6) + (5
30) + (12
MELSEC-Q
Station
number 8
3
Station
number 12
3
Local
Remote
station
I/O station
4.8) + (10
9.6)} +
5 - 2
1