6 PARAMETER SETTINGS
6 - 7
(g) Set the total number of connected stations in the CC-Link system including
reserved stations using "All connect count".
Default value : 64 (modules)
Setting range: 1 to 64 (modules)
Example) Set to 5 (modules).
(h) Set the number of retries using "Retry count", when a communication error
occurs.
Default value : 3 (times)
Setting range: 1 to 7 (times)
Example) Set to 5 (times).
(i)
Set the number of modules that can return to system operation by a single
link scan using "Automatic reconnection station count".
Default value : 1 (module)
Setting range: 1 to 10 (modules)
Example) Set to 2 (modules).
(j)
Set the station number for the standby master station using "Standby master
station No.".
Default value : Blank (No standby master station specified)
Setting range: Blank, 1 to 64 (Blank: No standby master station
Example) Set to blank (No standby master station specified).
(k) Set the data link status using "PLC down select", when a master station PLC
CPU error occurs.
Default value : Stop
Setting range: Stop
Example) Set to Stop.
(l)
Set whether the link scan for the sequence scan is synchronous or
asynchronous using "Scan mode setting".
Default value : Asynchronous
Setting range: Asynchronous
Example) Set to Asynchronous.
(m) Set the link scan interval using "Delay information settings".
Default value : 0 (Not specified)
Setting range: 0 to 100 (Unit: 50 µ s)
Example) Set to 10 (500 µ s).
specified)