Mitsubishi MELSEC-Q Series User Manual page 282

Cc-link system master/local module, mitsubishi programmable logic controller
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

APPENDIX
Sequence program
OFF
RISEND instruction
OFF
Completion device
OFF
Status display
device at completion
OFF
RYn
OFF
RXn
App - 21
(c) There are two types of interlock signals for the RISEND instruction: the
completion device (D2) and the status display device at completion (D2)+1.
1) Completion device
Turns ON in the END processing of the scan where the RISEND
instruction is completed, and turns OFF in the next END processing.
2) Status display device at completion
Turns ON and OFF depending on the completion status of the RISEND
instruction.
Normal completion : Stays OFF and does not change.
Abnormal completion: Turns ON in the END processing of the scan
END processing
END processing
ON
(d) Multiple dedicated instructions cannot be executed for the same station.
Since it takes several scans until the processing of the dedicated instruction
is completed, execute the next dedicated instruction after the completion
device has turned ON.
The next dedicated instruction executed before completion of the previously
executed dedicated instruction is ignored.
(e) The basic number of steps of the RISEND instruction is 10 steps.
(f)
The send buffer assignment is performed using the "Station information
setting" of the network parameters of the GX Developer. For more details,
see Section 6.2.
(2) Operation error
In the following cases, operation error occurs; the error flag (SM0) turns ON and
the error code is stored in SD0.
Error code
When the module specified by Un is not an intelligent function module.
2112
When the module specified by Un is not a special function module.
4002
When an attempt was made to execute an unsupported instruction.
4003
When the number of devices in the instruction is incorrect.
4004
When the instruction specifies a device that cannot be used.
4100
When the instruction contains the data that cannot be used.
When the number of data set to be used exceeds the allowable range.
4101
Or, when the storage data or constants of the device specified with the instruction
exceeds the allowable range.
where the RISEND instruction is completed, and
turns OFF in the next END processing.
Execution completion of
the RISEND instruction
Send completion
Receive completion
Description of operation error
MELSEC-Q
END processing END processing
ON
ON Abnormal
completion
Normal
completion
1 scan
App - 21