Delta AS Series Operation Manual page 431

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

Code
Indication
No network power supply for
F5
AS01DNET(RTU)
Internal error;
F6
An error in the internal storage
units of AS01DNET (RTU)
Internal error;
F7
An error in the data exchange
units of AS01DNET (RTU)
F8
Manufacture error
Internal error;
F9
An error in the access of the
Flash of AS01DNET (RTU)
E4
Module error
Repeated node ID detection
E7
The number of I/O modules
E9
connected to AS01DNET (RTU)
exceeds the maximum 8.
AS01DNET (RTU) is in STOP
80
state.
The AS01DNET (RTU)
83
configuration in the software is
being downloading.
C h a p t e r 1 2 Tr o u b l e s h o o t i n g
How to deal with
1. Check if the network cable is normal.
2. Check if the network power supply is normal. (The external
24V DC network power supply is connected between red
V+ and black V- of AS01DNET (RTU) .)
Return the product to factory for repair if the error still exists
after re-power on.
Return the product to factory for repair if the error still exists
after re-power on.
Return the product to factory for repair if the error still exists
after re-power on.
Return the product to factory for repair if the error still exists
after re-power on.
Check if an error occurs in the modules connected to the
right side of AS01DNET (RTU);
Check if the module exists;
Check if current module matches that configured in the
software;
Check if the unconfigured module is added.
If the code has emerged for a long time, please shoot troubles
in the methods below.
1. Ensure that there are at least two nodes working normally
in the network.
2. Check if the two ends of the network are both connected
with a 121Ω terminal resistor.
3. Ensure that the baud rates of all network nodes are same.
4. Check if the network cable has a problem such as being
disconnected and loosened.
5. Check if the bus communication cable length exceeds
maximum
transmission
transmission distance is exceeded, the stability of the
system can not be ensured.
6. Check if the shielded wire of the network communication
cable is grounded.
7. Turn on the power of AS01DNET (RTU) again.
Check if the number of I/O modules connected to AS01DNET
(RTU) is more than 8.
1. Check if the RUN/STOP switch of the PLC connected to
the DeviceNet master is turned to RUN.
2. Check if the value of control word of AS01DNET (RTU) is
1. For details, refer to section 10.5.4.3.4.
Wait until the download of AS01DNET (RTU) configuration
data is completed.
distance.
If
the
maximum
1 2 - 3 7
12_