Delta AS Series Operation Manual page 408

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

A S S e r i e s O p e r a t i o n M a n u a l
The remote communication IP address
6209
set in the UDP socket function is illegal.
The local communication port set in the
620A
UDP socket function is illegal.
_12
The device from which the data is sent
620C
in the UDP socket function is illegal.
The device which receives the data in
620F
the UDP socket function is illegal.
The data received through the UDP
6210
socket exceeds the device range.
There is no response from the remote
6212
device after the timeout period.
6213
The data received exceeds the limit.
The remote device refuses the
6214
connection.
6215
The socket is not opened.
6217
The socket is opened.
The data has been sent through the
6218
socket.
The data has been received through the
6219
socket.
621A
The socket is closed.
The device communication function
7011
code in COM1 is incorrect.
1 2 - 1 4
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > UDP
Socket.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > UDP
Socket.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > UDP
Socket.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > UDP
Socket.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > UDP
Socket.
Make sure that the remote device is connected.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > UDP
Socket.
Make sure the remote device operates normally.
Check whether operational sequence in the
program is correct.
Check whether operational sequence in the
program is correct.
Check whether operational sequence in the
program is correct.
Check whether operational sequence in the
program is correct.
Check whether operational sequence in the
program is correct.
1. Check the communication setting in the master
and the slave.
2. Check the communication cable.
-
X
-
X
-
X
-
X
-
X
-
X
-
X
-
X
-
X
-
X
-
X
-
X
-
X
-
H