The following table shows the data format of the SDO response message.
PLC device
D24000
D24001
Message Header
D24002
D24003
D24004
D24005
Message Data
D24006
D24007~D24031
Status code:
The following table lists the status code values in the response message.
Status code
0
1
2
3
4
5
6
7
8
9
0A
0B-FF
ResID: the same as the request ID in the request message.
Size: the length of the message data, maximum of 20 bytes. The unit is bytes. When writing, the
maximum is four; the data length is decided by the data type of index and subindex when reading.
Node ID: the node address of the target equipment on CANopen network.
Type: in the SDO response message, 43 (Hex) refers to reading four bytes of data; 4B (Hex) refers to
reading two bytes of data; 4F (Hex) refers to reading one byte of data; 60 (Hex) refers to writing 1/2/4
byte(s) of data; 80 (Hex) refers to stopping SDO command.
C h a p t e r 1 0 C A N o p e n F u n c t i o n a n d O p e r a t i o n
Response message
High byte
ResID
Reserved
Type
High byte of main index
Reserved
Datum 1
Datum 3
No data transmission request
SDO message transmission succeeds.
SDO message is being transmitted.
Error: SDO transmission time-out
Error: Illegal command code
Error: the length of the transmitted data is illegal.
Error: the length of the response data is illegal.
Error: Equipment to be sent messages is busy.
Error: Illegal type
Error: Incorrect node address
Error message (See the error code for SDO response message)
Reserved
Low byte
Status code
Size
Node ID
Low byte of main index
Sub-index
Datum 0
Datum 2
Reserved
Explanation
10
1 0 - 2 1